常州钟楼绿色数据中心位于江苏省常州市钟楼开发区桂花路以西、棕榈路以北、京杭大运河以东、华东云计算基地内,紧邻江宜高速,于2015年7月开工,设计等级新国标A级,2016年12月投入运行。

Changzhou Zhonglou Data Center is located in East China Cloud Computing Base, at the intersection of Guihua Road and Zonglv Road, east side of the Beijing-Hangzhou Grand Canal, adjacent to Shanghai-Nanjing Highway. The project  started construction work in July 2015. The 1st phase project opened in December 2016, the design level is  equivalent to grade A of the new national standard.




基础数据(DC 2#)
Basic Data

楼层
Floor

模块编号
Module No.

机柜数量(R)
Racks

模块面积()
Module Area

2

201~202

164 × 2

300 × 2

3

301~304

164 × 4

300 × 4

4

401~404

174 × 4

300 × 4

5

501~504

174 × 4

300 × 4

6

601~604

174 × 4

300 × 4

合计 Total

3072

5400




建设参数
Construction Parameters

  • 地理位置 Location

苏省常州市钟楼经济开发区桂花路22号
No. 2 Guihua Road, Zhonglou Economic Development Zone, Changzhou, Jiangsu






  • 建筑设计 Building

钢筋混凝土框架结构体系
Ferroconcrete frame structure

层高一层6.9m,二至六层5.6m
Story heights: 1st floor: 6.9m, 2nd-6th floor: 5.6m

地板承重12KN/㎡
Loading capacity: 12KN/㎡

专用货运电梯及货物卸载区,货梯载重3.5吨
Freight elevator (3.5 tons), loading bay

  • 电力系统 Power Supply

双路供电,供电容量40000KVA,支持定制电力改造
Dual paths, power supply capability: 40,000KVA, support electricity renovation

UPS系统2N冗余配置,满载后备电力15分钟
UPS system with 2N redundant configuration; UPS battery backup time at rated load: 15minutes

柴发采用N+1配置,满载后备供电12小时
Diesel generator with N+1 redundant configuration, operating 12 hours without refueling

单机柜电力10A~16A,局部可按需改造
Each rack power: 10A~16A; partial rack power could be expanded


  • 冷系统 Air Conditioning

机房使用精密空调调节室内温度和湿度
Precision air-conditioners control IDC temperature and humidity

空调系统采用UPS电源供电,空调冗余N+1
N+1 redundant air-conditioning system powered by UPS

地板下送风,上回风,冷通道封闭(冷热通道严格隔离)
Down-flow air supply, up-flow air return, enclosed cold passages (cold and hot passages are isolated)

水冷,给水中断的情况下系统24小时的正常运行;蓄冷罐15分钟不间断制
Water cooling system operates 24 hours without water supply; cold storage tank provides 15 minutes’ cooling in case chillers fail

  • 消防系统 Fire-Fighting

采用IG541自动气体灭火系统
IG541 automatic gas fire-fighting system

分区相互独立,可以实现分区灭火,此外配备手持式灭火器及空气呼吸器
Independent zone for fire-fighting separately, each zone equipped with handheld extinguisher and air-breather

与空调、新风、门禁、计算机供电和市电等系统联动
Linked air-conditioning, air, access control, computer power supply and city power etc. system

  • 安保系统 Security

可根据用户需求定点增加高清摄像设备
HD cameras could be added as needed on spot

授权门禁系统、红外探测,支持重点区域设施改造
Access control system, infrared detection, renovation for key area infrastructure

人员权限设置,设备安全管理,多层安全防范与管理
Staff permission setting, devices safety management, multi-levels security protection and management

  • 网络环境 Connectivity

中国移动等
Backbone network link to China Mobile

多线均万兆对接,可随时根据实际需求进行扩容
Tens of gigabit multiline, scalable as needed

提供144芯裸纤资源,可支持链路改造
144 core bare fiber resource, supporting link renovation



  • 管理服务 Management

7×24小时值守,5 分钟内响应,15分钟内应急处理反馈
7×24 hours guarding, quick response in 5 minutes, emergency processing and feedback in 15 minutes

拥有完备的应急方案、完善的应急管理流程,切实保障业务连续性
Complete emergency solutions and emergency management process to guarantee business continuity